MoistAirTab™ Example 3 - Heating

Example 3

Moist air, saturated at 2°C, enters a heating coil at a rate of 10 m3/s. Air leaves the coil at 40°C. Find the required rate of heat addition.

Solution

The solution is presented below as a table generated from Excel. The gray shaded areas represent the input data.

Soution: Units Inlet Outlet
Total pressure bar 1.01325 1.01325
Dry bulb temperature °C 2 40
Wet bulb temperature °C 2 40.00
Volume flow rate m3/s 10.00 11.39
       
Humidity ratio kgw/kgdry air 0.0044 0.0044
Volume of moist air m3/kgdry air 0.7845 0.8932
Mass flowrate (dry air) kgdry air/s 12.7463 12.7463
Enthalpy of moist air kJ/kgdry air 12.98 51.53
Total enthalpy flow kJ/s 165.45 656.86
       
Heat added kW   491.42