MoistAirTab™ Example 4 - Cooling

Example 4

Moist air at 30°C dry-bulb temperature and 50% relative humidity enters a cooling coil at 5 m3/s and is processed to a final saturation condition at 10°C. Find the kW of refrigeration required.

Solution

The solution is presented below as a table generated from Excel. The gray shaded areas represent the input data.

Soution: Units Inlet Outlet
Total pressure bar 1.01325 1.01325
Dry bulb temperature °C 30 10.00
Relative humidity % 50% 100%
Volume flow rate m3/s 5.00  
Wet bulb temperature °C 22.00 10.00
       
Humidity ratio kgw/kgdry air 0.0134 0.0077
Volume of moist air m3/kgdry air 0.8770 0.8116
Mass flowrate (dry air) kgdry air/s 5.70 5.70
Enthalpy of moist air kJ/kgdry air 64.35 29.35
Enthalpy flow   366.89 167.34
       
Amount of condensate removed kgw/kgdry air   0.0057
Condensate flowrate kgw/s   0.0325
Condensate specific enthalpy kJ/kgw   42.01
Condensate enthalpy flow kJ/s   1.37
       
Referigeration required kW   198.18